Gas extraction requirements
 
In compliance with the B.F.P.S.A. Code of Practice, enclosures protected against fire by gas extinguishing systems must be provided with a means of extracting the gas or post – fire atmosphere to open air. 

Independent, normally closed, mechanical ventilation with extraction provides the most efficient solution and for liquefiable gases with high boiling points, such as FM-200, the room atmosphere should be vented from low level.
  
 

 
 
Ventpac self contained system
 
As a means of complying with this directive without the need to install a specialist engineered system, GIELLE Fire Engineering are able to offer the self contained VENTPAC extraction unit. Designed to suit enclosure sizes up to 250m³ with or without voids, the VENTPAC extract unit provides a minimum of four air changes per hour.
 
Installation simplicity
 
Simplicity of installation is a major feature of VENTPAC. Contained within a Zintex metal enclosure, the unit houses a high airflow centrifugal fan and positive shutoff damper with motor and is very quiet in operation. All components are electrically pre-wired to the external terminal box for direct connection to remote fireman’s switch or control facilities.

VENTPAC is complete with a telescopic transition duct, requiring only a 250mm diameter aperture to be provided and automatically allows for various external wall thickness without the need for any specialist site fitting work. The discharge duct terminates externally to a GIELLE got connection fascia plate which is complete with a back draught flap.
 
Dual path extract
 
Room atmosphere is extracted through the louvered grille, positioned in the end plate of VENTPAC. Where floor void extraction only is required, a quick release baseplate can be removed and interchanged with the extract grille. For situations where simultaneous room and floor void extraction are required, partial removal of the baseplate allows dual enclosure extraction.
 
System Specification
 
 
 
Pressure relief requirements
 
Fixed fire extinguishing systems employing inert gases extinguish fire by reducing the oxygen content of the protected space. To achieve this, a volume design concentration of 35% or more is normally required.

Injection of this high concentration results in a positive pressure, which displaces the atmospheric air from the room. To compensate for this over – pressure, system manufacturers generally specify that suitable venting should be provided to alleviate any risk of structural damage.
 
Pressure relief design
 
As part of the system design programme, a calculation is made for the appropriate system size, of the venting area required to prevent any damaging over – pressurisation. System manufacturer tests and data have established that normal build rooms will withstands an increased pressure of 5mb (500 Pascals).

Any a means of complying with these requirements, GIELLE Fire Engineering are able to offer the PRESPAC pressure relief unit. Specially designed for use with fixed gas extinguishing systems PRESPAC will open automatically when the positive pressure reaches 1.5 mb (150 Pascals). As pressure equalises the weighted relief blades close to seal the enclosure and maintain the extinguishing concentration.
 
Fire rating integrity
 
The BFPSA Code of Practice stipulates that rigid elements of the protected enclosure must have a fire resistance of not less than 30 minutes. Often to comply with this directive it is necessary to install a separate fire damper, in addition to the pressure relief unit, which in the event of operation defeats the object of fitting any over pressure device.

PRESPAC will maintain fire wall integrity without the need to fit a separate damper. The unit has been independently tested by Chiltern Fire to the general requirements of BS478: Part 20: 1987, where it achieved over two hours integrity.
 
 
send us an email

 info@gielle.it
* send us a fax 

 +39 080.3101309
call us  

 +39 080.3118998
 
 
Gielle Srl - Administrative Headsquares  
Via R. Ferri 32 Z.I. - 70022 Altamura (Ba) Italy
Tel +39 0803118998 - Fax + 39 0803101309
E-mail: info@gielle.it - Save in outlook
Free Number
 
 
 
Website of Gielle Group - Privacy - © 2009 Gielle Srl - created by www.omnilink.it